CME 2 User Guide Gain Scheduling
Copley Controls 227
H.3: Gain Scheduling Table Guidelines
A Gain Scheduling Table contains a progression of Key Parameter values and
corresponding gain adjustment values.
H.3.1: Gain Schedule Table Storage Limits
The maximum number of lines (gain adjustment specifications) that can be stored in the
Gain Scheduling Table is 1000. A typical Gain Schedule Table will contain far fewer lines.
The number of Gain Scheduling Table lines is limited by the amount of CVM memory
space available in the amplifier. A Gain Scheduling Table loaded into the amplifier shares
that space with Copley Virtual Machine (CVM) programs and Camming Tables. Therefore,
the maximum number of Gain Schedule Table lines will decrease if CVM programs or
Camming Tables are stored in the amplifier.
The Gain Scheduling screen Tables tab displays the percentage of amplifier memory
used:
H.3.2: Gain Schedule Data Rules
All must be whole numbers (no fractional values).
All Key Values must be increasing.